Supplied with an integral pre-wired junction box, the detector can be installed using conduit or cable and glands depending on individual site standards.
Both the TR-98M and TR-98S are housed in explosion-proof enclosures rated for use in Class 1, Division 1, Groups B,C and D hazardous areas.
Sensor transmitters typically provide a 4-20 mA output, and this signal can be fed to a controller which provides alarm processing and relay contacts to trip alarm horns/lights, activate ventilation motors, etc. However, some applications require relay contacts to be located at the sensor transmitter itself. For these applications, the TR-98M Transmitter Relay provides a simple solution. Even though it is designed for IST transmitters, it will also work with other transmitters which produce a 4-20 mA signal.
The TR-98M (master) incorporates a conduit fitting which enables it to attach directly to either the SM95 or 4-20IQ transmitter, and provides one Single-Pole Double-Throw (SPDT) relay contact. A seven segment DIP switch allows you to program the relay to trip at a designated value within the 4-20 mA signal range. If additional relay contacts are needed, the TR-98S (slave), a slave relay module, can be added. Up to four TR-98S units can be added, providing a total of five relay contacts.
A seven-segment DIP switch (S1) is used to set the alarm point from 1% to 100% of full scale. Each switch has the following values when in the OPEN position.
Switch positions are clearly marked on the DIP switch package.
The alarm set point is the sum of the values in the OPEN position. For instance, for an alarm set point of 20% of full scale, switches 3 and 5 should be in the OPEN position while the rest of the switches should be closed. This yields S3 (4%) + S5 (16%) = 20%. With a 4-20 mA output, this would mean an alarm set at 7.2 mA.
Unless specified, all TR-98 modules are shipped with relays in Normal mode.